19'' 6U Chassis page 21/71
• Check the inventory to verify type of XFP currently installed. Consult the
object:
ms43062XMRinvXfp
Location: ...\microsens\ moduleMS43062XM\ ms43062XMri\
• Take the necessary steps to minimise the impact on your network, traffic by-
pass re-route etc.
• Disable the line by setting the object:
ms43062XMCtrlXfp1Onoff
Location:
\microsens\moduleMS43062XM\ms43062XMcontrolsWrite\
ms43062XMCtrlxfp1Onoff\
• Remove the Fibre Optic connector
• Release the XFP by: Carefully opening the latch or pressing the locking
button and slide the XFP out of the module and place it aside
• Gently push the XFP into the relevant module port until it is securely seated.
Take care to insert the XFP respecting the orientation described in the
following picture.
Do not remove the protective caps from the XFP until you are ready to attach
the network fibre-optic.
• If Latch-Type XFP; Close the latch to lock it into place
• Clean Fibre Optic connectors on fibre optic cable
• Re-connect Fibre
• Enable port by re-setting the object:
ms43062XMCtrlXfp1Onoff
Location:
..\microsens\moduleMS43062XM\ms43062XMcontrolsWrite\ms43062XMCtrlxfp1O
noff\
• Verify correct operation of the XFP
End procedure